NewFound Energy Ltd : Energy Monitoring, Management and Control NewFound Energy Ltd - Energy Saving by Analysis

Portable Energy Monitoring & Recorders

Home | Products | Why Monitor | How It Works | Download | Latest News | Contact Us | Site Map | About Us |
ATLAS Energy Monitoring Systems | Profile Portable Energy Monitor | ATLAS Load Control | Data Loggers | Electricty Meters

Portable Energy Monitoring / Recorders

The Profile range is for use anywhere on a site to monitor and record energy use in an electrical circuit. It is easy to install and the integral L.C.D confirms measurements being made.

The Profile is available for purchase or hire to perform short duration usage surveys or use as a temporary electricity meter and comes with the Propower PP2 system software for data analysis.

THE SYSTEM
Profile measures current and voltage and records, against a user set integration period, kW, kVAr, supply Volts, total circuit Power Factor and two Pulse Inputs.
Using this recorded information the Propower PP2 software provides the ability to graph and print information, for all 3 phases or a single phase, on kW, kVAr, kVA, Amps, Volts, and Power Factor.

Data is stored in user selectable integration periods between 1 & 30 minutes with a capacity of up to 12 weeks.

There are no full scale % accuracy problems with Profile when measuring low currents - Profile IV automatically chooses between the ranges of 0-6 Amps, 0-120 Amps, 0-500 Amps or 0-2000 Amps to suit the current being measured.

PROPOWER PP2 SOFTWARE
This Windows based software provides for data retrieval, viewing of data in both tabular and graphical form and printing if required. It is also the means to changing Profile operation configuration such as integration period, time etc.
Data can be graphed for individual phases, collectively for all three phases or as a total for the circuit.
A real time monitoring facility is also available

The data file can also be imported into spreadsheets such as Excel, Lotus123 etc for specific analysis as the user may require or the well known Reporter software package can be used.

SYSTEM SPECIFICATION

  • Profile unit 95 x 195 x 45 mm with integral LCD, weight 0.5 kg
  • Integration period user selectable 30, 15, 10, 5, 1 mins or 10, 2 secs
  • Data storage 30 mins : 12 weeks, 15 mins : 6 weeks etc
  • Profile IV auto ranges to 6, 120, 500 & 2000 Amps
  • Profile V as IV plus with auto HV facility
  • 3 Rogowski coils, internal capacity ø 65mm, 0-2000 Amps range
  • LV power lead [standard 13 Amp plug], unit will operate 95V to 265V
  • RS232 data transfer lead
  • Carry case and User Manual
  • Propower PP2 Software with User Guide

Options available include pulse input adaptor and fused mains lead/probes.
An additional software package, Reporter Professional, provides further data analysis including tariff costing of the data recorded and other graphical outputs.
Data can also be retrieved over a site network thus enabling the monitoring of remote locations from a central PC.

For more information download our leaflet on the Profile or contact us.

Qualified for Energy Technology List - Link

The ETL symbol is a UK registered certification mark of the Carbon Trust.

Profile Picture

Propower Software Rreport Summary

ProPower Software Graph